Spesifikasi

Amperage DC
Rentang pengukuran: 0 - 50; 0 - 100; 0 - 200
Akurasi: +/- 3% skala penuh
Pasokan sensor: 15-30 V AC / DC
Isolasi: 600 VAC rms
Rentang suhu operasi: -15 sampai 600C (5 sampai 1400F)
Kelembaban jangkauan: 10 - 90% non-kondensasi
Waktu respon: 2 dtk.
Output: dipilih 4 -20mA atau 0 - 5VDC
Pasokan saat ini: 35 mA max.
Dimensi: 2.90x2.58x1.06 masuk (74x66x27 mm)
Berat: 4 oz.
Pembukaan sensor: 1.10x.90 inci (28x23 mm)
Indikasi LED: Pulse = Norm; Mati = Tidak ada Kekuatan; Solid On = Over Range