Tersedia puluhan seller menjual Kyoritsu Earth Resistance & Resistivity Tester 4106 paling lengkap dan terpercaya. Harga Kyoritsu Earth Resistance & Resistivity Tester 4106 18500000. Ayo belanja sekarang!
Earth resistance measurement with six ranges covering measurements from 0.001 to 200k.
Earth resistivity() measurement is automatically calculated after having set the distance between Auxiliary Earth Spikes (Wenner method).
Automatic and Manual selection of the Test Current Frequency in four bands of 94/105/111/128Hz. In Automatic mode KEW 4106 will select the most suitable Frequency.
Advanced Filtering method (based on FFT Fast Fourier Transform) reduces noise interference for obtaining stable measurements.
Up to 800 measurement results can be saved in the memory and recalled on the display.
The stored results can be transferred to a PC via USB adaptor (Model 8212-USB) by using software KEW Report which are included.
Robust design with IP54 protection.
SPECIFICATIONS
Function
Range
Resolution
Measuring range
Accuracy
Earth resistance Re (Rg at ? measurement)
2?
0.001?
0.03 - 2.099?
?2%rdg?0.03?
20?
0.01?
0.03 - 20.99?
?2%rdg?5dgt (*1)
200?
0.1?
0.3 - 209.9?
2000?
1?
3 - 2099?
20k?
10?
0.03k - 20.99k?
200k?
100?
0.3k - 209.9k?
Auxiliary earth resistance Rh, Rs
8% of Re+Rh+Rs
Earth resistivity ?
2?
0.1??mm - 1??m Autoranging
0.2 - 395.6??m
?=2???a?Rg (*2)
20?
0.2 - 3956??m
200?
20 - 39.56k??m
2000?
0.2 - 395.6k??m
20k?
2.0 - 1999k??m
200k?
Series interference voltage Ust (A.C only) (*3)
50V
0.1V
0 - 50.9Vrms
?2%rdg?2dgt (50/60Hz)
?3%rdg?2dgt (40 - 500Hz)
Frequency Fst
Autoranging
0.1Hz 1Hz
40Hz - 500Hz
?1%rdg?2dgt
Measuring method
Earth resistance: Fall-of-potential method (currents and voltages measured via the Probes) Measurement method of Earth Resistivity (?): Wenner 4-pole method Series interference voltage (earth voltage) RMS Rectifier (between the E-S Terminals)
Memory capacity
800 data
Communication Interface
Model 8212-USB Optical Adaptor
LCD
Dot-matrix 192?64 monochrome
Over-range Indication
"OL"
Overload Protection
between E-S(P) and between E-H(C) terminals AC280V / 10 sec.